Abstract

A stochastic method is presented in this paper to estimate the future voltage unbalance in a low-voltage distribution network with high-penetration of single-phase photovoltaic inverters (PVIs). Location and phase allocation of the PVIs are considered as input parameters for the stochastic simulation. The method has been applied to three different low-voltage networks: two in Sweden and one in Germany. In the Swedish networks, for 6-kW single-phase PVIs, it is likely that the contribution from single-phase photovoltaic inverters to the voltage unbalance exceeds 1%. The 2% value is unlikely to be exceeded. In the German network, for 4.6-kW single-phase PVIs the voltage unbalance is between 1.35% and 2.62%. The risk of high voltage unbalance can be reduced by a combination of controlled distribution over the phases and reduction of the maximum size for a single-phase PVI.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.