Abstract

An experimental investigation has been carried out to find the nature of temperature profiles of the process and cooling fluids during steam condensation across the port to channel in plate heat exchangers (PHEs). In the present study, low corrugation angle (30°) plates have been used for different plate package of PHEs with 41 and 81 plates. The process steam entered at 1 bar with a small degree of superheat. Water has been used as the cold fluid. A traverse temperature probe is inserted into both inlet and outlet ports of the plate heat exchanger. The temperature of the process steam and cooling fluid have been measured and recorded at the location of first, middle and last channels for different inlet and exit flow conditions for each plate package of the heat exchanger. Also, the overall pressure drop has been measured at different conditions at the outlet of the process steam, i.e., full and partial condensation. The traverse temperature measurements have indicated that there is a considerable variation in temperature along inlets and outlets of process steam and cooling fluid, due to flow maldistribution. The experimental data has been analyzed to show how the flow distribution on the cooling side affects the condensation of steam in plate heat exchangers. The present results will help to study further the nature of steam condensation in parallel channels of heat exchangers.