Abstract
In the piping between the tank of a 40 MVA transformer, originally designed for ONAN/ONAF cooling combination, and its bank of radiators, a propeller oil pump was installed. Characteristic temperature rises were measured before and after installation of the pump. The results were applied to the development of a new algorithm for calculation of windings and oil steady-state temperature rises of ONAN/ONAF/OFAF transformers. The mathematical model is briefly described in the paper, and the basic thermal characteristics of transformers with this combination of cooling types are described. Installation of the oil pump can make transformer cooling more efficient provided that certain conditions are satisfied.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEE Proceedings C Generation, Transmission and Distribution
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.