Abstract
In this study, a static synchronous compensator (STATCOM) along with a variable frequency drive (VFD), is proposed for voltage and frequency control of a small-hydro turbine driven self-excited induction generator (SEIG) system. STATCOM is used to control SEIG terminal voltage through variable reactive power injection. A control algorithm based on adaptive noise cancellation filter is proposed for STATCOM control. A field oriented controlled VFD feeding an induction motor is used to control system frequency. The VFD consumes active power in excess of consumer loads and thereby it regulates the system frequency. The excess power consumed by the VFD is utilised for pumping water to either an overhead storage tank or irrigation purposes. Besides the voltage control as primary objective, the STATCOM also provides harmonic currents compensation and load balancing under unbalanced non-linear loads. The proposed method of voltage and frequency control using STATCOM-VFD combination is implemented on a 3.7 kW SEIG and the test results are presented to demonstrate its performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.