Abstract

Five large-scale fire tests were conducted to investigate the effects of ceiling clearance, sprinkler type and sprinkler discharge rate on sprinkler fire control performance of a non-storage high-ceiling-clearance scenario. The fire scenario selected for this study is to simulate fire loads of either sale booths or exhibition booths in non-storage occupancies under a high ceiling. Three ceiling heights were employed: 12, 16 and 18m. Two Large Orifice (LO) sprinklers, an Extra Large Orifice (ELO) sprinkler and a K363 Control Mode Specific Application (CMSA) sprinkler were used. All the sprinklers tested are pendent sprinklers with a nominal temperature rating of 70°C. The sprinklers were installed at 3m×3m spacing. The effectiveness of fire control of the sprinklers depends on ceiling height, sprinkler spray pattern, water drop size (as related to orifice size and discharge pressure), and sprinkler discharge rate. The test results show that the standard-response LO sprinklers at a discharge rate of 141L/min per sprinkler did not control the test fire under a 12 m high ceiling and sprinkler skipping occurred. For a ceiling height of 16 m, the quick-response LO sprinklers discharging at a rate of 182L/min per sprinkler were not effective in controlling the test fire and sprinkler skipping also occurred; however, the standard-response ELO sprinkler discharging at a rate of 209L/min was marginally effective in controlling the test fire. For a ceiling height of 18 m, the K363 CMSA sprinklers discharging at a rate of 363L/min per sprinkler either controlled or suppressed the test fire, because the sprinkler generates considerably large water drops and provides sufficient high discharge rate. The test series has demonstrated that water drop size is an important factor for achieving fire control or suppression of the high-ceiling-clearance fire scenario. With regard to the fire size at sprinkler actuation, the convective heat release rate of the fire is estimated from the gas temperature measured at ceiling level directly over ignition by using a plume correlation. Using a sprinkler with a RTI of 130 (m⁎s)1/2 under the 18 m high ceiling, the fire size at first sprinkler actuation was estimated to be 7-8 MW. The test results provide a technical basis for developing sprinkler installation rules for non-storage high-ceiling-clearance occupancies in the revised Chinese National Code of Designs for Sprinkler Systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.