Abstract
This paper presents a methodology for specifying the winter and summer peak-load limits for substation transformers that carry a temperature-sensitive load, taking into account the random nature of load and ambient temperature as well as their correlation. With this methodology, we can easily and accurately specify the peak-load limits for each substation transformer once the historical ambient temperature and load data are available. Also, we can collectively specify the peak-load limits for the transformer of each cooling type (OA, OA/FA, or OA/FA/FA) in a geographic region based on the mean and standard deviation of ambient temperatures in that region. Such peak-load limits are useful for power system planning.