Abstract

This paper presents figures for the small power equipment loads encountered by the Welsh School of Architecture in UK offices while undertaking a programme of research and monitoring into the energy efficiency of air-conditioning systems in use. The findings are based on surveys undertaken in 30 air-conditioned offices between April 2000 and October 2002. Peak small power equipment loads were calculated using the CIBSE nameplate-ratio method. The results show that the small power loads averaged 17.5 W/m 2 with a range between 6 and 34 W/m 2 of treated floor area. When normalised for occupancy the calculated peak small power equipment loads averaged 158 W per person, with a range between 124 and 229 W per person. Current industry guidance could lead to the overestimation of small power equipment loads by as much as 650%, ultimately resulting in increased capital and running costs of air-conditioning plant and reduced thermal comfort. A more accurate method of estimating peak small power equipment loads in UK office buildings is suggested based on occupant density.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.