Abstract

Geomagnetically induced currents (GICs) can cause transformer half cycle saturation and consequently affect the power grid with harmonic currents and increased reactive power loss. This paper focuses on using transformer neutral GIC measurements to help validate the GIC models. A linear GIC model is presented that relates the geoelectric field input to the transformer neutral GICs. To validate this model, a temporal GIC matrix model is introduced and the singular value decomposition (SVD) is used for estimating the geoelectric field. The effectiveness of the approach is shown using a 20 bus test case. Finally, the GIC model is extended to account for nonuniform electric field and its accuracy is evaluated through SVD.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.