Abstract

In this paper, a PWM scheme for three-level full-SiC uninterruptible power supplies (UPSs) has been developed to achieve a high power-density. Two key passive components have been selected for size reduction of the full-SiC UPS; common-mode (CM) EMI filter and dc-link capacitors. To reduce the CM noise, a new vector combination has been proposed based on a synchronous switching of three-phases. The proposed combinations align CM voltage (CMV) to be a single pulse per a switching period. CMV cancellation between a three-level rectifier and inverter can be maximally utilized while a drift of neutral point voltage can be prevented by transition among three combinations. Secondly, to reduce dc-link capacitors, a simple algorithm to compensate neutral point voltage fluctuation has been proposed both for differential-and common-mode output voltage. The proposed algorithm can simply be implemented by a correction on carrier-slopes and injected zero-sequence voltage. The proposed scheme has been verified with 20 kW full-SiC UPS switching at 60 kHz with 146 μF dc-link capacitors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.