The temperature field distribution in the medium-voltage vacuum interrupter decides the thermal stability of it. In this paper, the simulation model of a kind of 12kV/3150A/40kA medium-voltage vacuum interrupter is constructed, and conductive bridge model is used. This paper simulates current contraction and Joule heating between contacts, and solves relevant problems using the function of the thermal-electrical coupling in the finite element software ANSYS. Steady-state temperature rise of vacuum interrupter at rated current and transient temperature rise of vacuum interrupter at short-time withstand current are calculated. Influence of the contact situation on vacuum interrupter temperature rise is analyzed. Steady-state temperature rise experiments for the interrupter are carried out, and experiment results verify the accuracy of simulation results. The results are useful in the designing and optimizing of medium-voltage vacuum interrupter.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.