Abstract
Abstract Aim at the three times simultaneous commutation failure of two Multi-outfeed and Multi-infeed DC Systems in a Similar Path of Ningxia, the Ningxia power grid model is built in Power System Analysis Software Package (PSASP) with actual parameters, and the accident inversion simulation is carried out based on the operation state of the power grid before the fault. Based on the inversion simulation, the simulation results were compared with the measured PMU data. The results showed that the trend of simulation and the measured curve is consistent, and the simulation was slightly more serious than the actual fault, but the overall error was less than 10%, which verified the accuracy of the simulation model and method, and provided a basis for the subsequent simulation analysis of the power grid operation mode.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have