Abstract

In this article, we propose the endothermic screen model. The aim is to reduce the problems of the high temperature and low utilization of waste heat in industrial plants with high radiant heat. In this paper, the Rhino software is used to establish the model and import it into the FLUENT software, divide the mesh, set the boundary conditions and analyze the transient temperature field. Finally, the temperature change law in the plant and the waste heat recovery efficiency of the endothermic screen are obtained. The flow of cooling water in the endothermic screen is used to transform and transfer the high-radiation heat inside the plant to the outside. The simulation results show that after adding the endothermic screen, the average indoor temperature drops from 313.33 K to 305.66 K, which has a cooling effect. The waste heat recovery efficiency reaches up to 56%, and the waste heat recovery effect is obvious. The research results can provide a reference for the application of an endothermic screen in actual high radiant heat plants and provide a more comfortable working environment for the plant workers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.