Abstract

The objective of this paper is reduced the electrical energy which used in air-condition system by replaced the common roofing system by the another which more suitable for hot climate area. The researcher was build (1x1x3)m sample room at 3rd floor in building at Baghdad city (33.2 °N) for 200mm polystiran thermal insulation for other room surfaces and air-conditioner of 0.5 Ton of refrigeration capacity is used to maintain the standard thermal comfort, the roof thermal behavior study for 15 hr/day, at day 21 from five each months (Jan, March, June, July & September). It was found the suggested roofing system reduced the dead load by 300kg/m2 and the electrical energy which used in air-conditioning system reduced by 37% when used open air gap was used, and become 30% when has used closed air gap has used and became 27% relation to ordinary system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.