Abstract

PurposeThis study aims to focus on an adaptive method for fault detection and classification of fault types that trigger in three-phase transmission lines using artificial neural networks (ANNs). The proposed scheme can detect and classify several types of faults, including line-to-ground, line-to-line, double-line-to-ground, triple-line and triple-line-to-ground faults.Design/methodology/approachThe fundamental components of three-phase current and voltage were used as inputs in the ANNs. An analysis of the impact of variations in the fault resistance, fault type and fault inception time was conducted to evaluate the ANNs performance. The survey compares the performance of the multi-layer perceptron neural network (MLPNN) and Elman recurrent neural network trained with the backpropagation learning technique to improve each of the three phases of the fault detection and classification process. A detailed analysis validates the choice of the ANNs architecture based on the variation in the number of hidden neurons in each step.FindingsThe mean square error, root mean square error, mean absolute error and linear regression are measured to improve the efficiency of the ANN models for both fault detection and classification. The results indicate that the MLPNN can detect and classify faults with a satisfactory performance.Originality/valueThe smart adaptive scheme is fast and accurate for fault detection and classification in a single circuit transmission line when faced with different conditions and can be useful for transmission line protection schemes.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call