Abstract
In the paper, the short-circuit forces acting on three tubular conductors arranged in an equilateral triangle and constituting a 3-phase system enclosed by a cylindrical aluminium enclosure are examined. The relations for the time functions of the short-circuit forces are developed taking into account the transverse dimensions (diameter) of the conductors. The forces acting on such structures are compared with the forces on structures with filamentary conductors; it results that for usual structures the assumption of filamentary conductors causes a small error in the values of forces; for practical computations the simpler relations that concern forces on filamentary conductors can be used.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.