Abstract

Superconducting current limiters (SFCLs) can limit short-circuit fault current and provide sufficient time for DC circuit breakers (DCCBs) to isolate faults. An SF 6 passive resonance DCCB combined with a superconducting current-limiting module and a DC interruption module is proposed due to the high current interruption properties and the low on-state loss. However, experimental investigations of SF 6 passive resonance DCCBs combined with SFCLs using DC source are currently lacking. The objective of this paper is to obtain the interruption characteristics and modeling design methods of the proposed SF 6 passive resonance DCCB. This paper designs a 10 kV SF 6 passive resonance DCCB and tests the DCCB in a 10 kV/10 kA circuit. Quenching resistance and arc models are established based on experimental results. Experimental results show that the superconducting current-limiting module responds fast at 0.3 ms and limits the DC fault current of 10 kA to a peak of 816 A. Then the DC interruption module interrupts the limited current successfully. Besides, there is no overvoltage afterward in all the tests because the superconducting current-limiting module absorbs much of the energy during the interruption. The proposed DCCB would be an effective method for interrupting short-circuit faults in high voltage DC systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.