Abstract
Impedance-based analysis methods are widely applied to the small-signal stability analysis of grid-connected converters. As the initial step to carry out the impedance-based stability analysis, it is critical to select whether to represent the converter as a Norton or Thevenin equivalent circuit. However, there is lack of definition on the representation of converters, and inappropriately selected impedance model choice leads to improper stability analysis. Moreover, existing impedance-based stability analysis methods, e.g., return-ratio matrix (RRM)-based method, only apply to minimum phase systems where the RRM does not contain right-half-plane poles. In complex and power-electronics-dominated power systems, interactions between multiple converters lead to nonminimum phase power systems, where current methods can no longer be directly applied. To address these problems, a stability criterion is proposed by introducing the concept of settling angle. As the main contribution of this article, the settling angle of total admittance is proven as the intrinsic hallmark of power systems and directly reflects the system stability. The proposed settling-angle-based stability criterion is validated by control hardware-in-the-loop experimental results for a three-terminal system that integrates grid-forming and grid-following converters through a common bus.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.