Abstract
The application of a sequential switching scheme for the mitigation of capacitor switching transients is presented. The method utilises neutral grounding impedance connected at the neutral point of the switched capacitor bank together with sequential pole switching. The neutral impedance is sized to minimise the open-circuit contact voltage of the capacitor breaker phases. Theoretical analysis of the proposed scheme has been carried out together with computer simulation. In addition, neutral impedance sizing criteria are presented in order to achieve minimal transient over-voltage caused by capacitor switching. The proposed method was found capable of reducing the transient over-voltage at the utility switched capacitor location to 1.07 and 1.12 p.u. at the customer load bus.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.