Abstract

When the load generated harmonic, unbalanced, and reactive power is beyond the limited capacity of a thyristor-controlled LC -coupling hybrid active power filter (TCLC-HAPF), the TCLC-HAPF with the conventional control methods cannot provide satisfactory compensation performance. In this paper, a selective compensation control method of harmonic distortion, unbalanced and reactive power of the TCLC-HAPF is proposed, which can function even at different voltage conditions (e.g., voltage dip, voltage fault, etc.). First, the proposed control method decomposes the load power into fundamental positive-sequence reactive power, fundamental negative-sequence power (unbalanced power), and harmonic power. Then, the decomposed reactive, unbalanced, and harmonic power can be selectively or fully compensated based on the capacity of the TCLC-HAPF. Finally, simulation and experimental results are provided to verify the effectiveness of the proposed selective compensation control method for the TCLC-HAPF.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.