Abstract

This article describes a method for selecting the parameters of AC and DC filters for a multi-terminal HVDC transmission system based on voltage source converters (VSC-HVDC). The equivalent circuit model of a multi-terminal VSC-HVDC system with the parameters ±500 kV and 500 MW was developed in the Matlab Simulink software package and presented in d-q coordinate axes. The system voltage source converters in the model were controlled using a three-level pulse-width modulation (PWM) to reduce the level of current and voltage higher harmonic components and decrease the capacity of AC and DC filters. To select the most efficient filter for use as part of a multi-terminal VSC-HVDC system, high-pass filters (HPF) and low-pass filters (LPF) were considered.