Abstract

This paper deals with the seismic vulnerability of high voltage equipment typically installed in electric substations. In particular, the seismic response of a 380kV vertical disconnect switch has been investigated based on the results of an experimental campaign carried out at Roma Tre University. According to a series of non-linear analyses, the influence of the most significant parameters on the seismic behavior of this apparatus has been analyzed and the corresponding fragility curves have been evaluated by using the Effective Fragility Analysis method. The results showed a limited vulnerability of the disconnect switch, whose most critical parts are the bottom joint of the ceramic support column and the steel column base.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.