Abstract

Electrical substations and vital components, e.g., disconnect switches, experienced severe damage that caused blackouts during past earthquakes. To improve the seismic resiliency of power grids and use probabilistic decision-making frameworks, comprehensive fragility data for the different substation equipment are needed. The objective of this study is to investigate the seismic performance of and develop component and system fragility curves for a critical substation component: disconnect switches. The seismic vulnerability of two common switch types was evaluated and two operational configurations were considered. Detailed nonlinear finite element models for the full switches were calibrated using previous experimental data and used to conduct incremental dynamic analysis and carry out the fragility assessment. A total of 160 triaxial ground motions representing four sets of different ground motion characteristics were used. The switches’ fragility curves were developed and presented to be readily used for new substation design, prioritizing retrofit/maintenance activities and reliability assessment of power grids.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.