Abstract

One significant disadvantage of the doubly fed induction generator (DFIG) is its high vulnerability to grid faults, which can be attributed to the direct linkage of its stator windings to the electrical network. The electromagnetic pairing of the stator and rotor in the DFIG implies that a voltage dip causing excessive stator current results in high currents in the sensitive back-to-back inverters and an overcharge in the DC-link capacitor. A comparative study of two protection configurations with a sliding mode non-linear control (SMC) for the rotor transient current for the better operation of the DFIG under network faults is presented in this document. One conventional configuration consists of a crowbar with DC-chopper and another is changed by adding to the crowbar an RL series device known as an appropriate protection configuration (APC). Both are placed within the rotor windings and ride-side converter (RSC) to achieve secures and maintains SMC of DFIG. The comparison of the results reached with the MATLAB/ SIMULINK application is evidenced by the success of these two configuration reduce the high rotor current and DC-link voltage. Additionally, the conventional configuration, in conjunction with the APC, diminishes the current RSC to levels below 0.2kA and exactly 2.25kA, while also being capable of absorbing up to 2.52kA and 1.3kA in the event of a grid fault. So the main difference is that with the APC, the decoupling of the RSC to the rotor in the presence of a fault can be averted, thereby assuring the control of all stator power via the RSC converte.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call