Abstract

Searching the Damaged Outgoing Feeder in Networks with Insulated Neutral by Phase-to-ground FaultThe method of searching the damaged feeder was improved by alternate disconnecting of feeder circuit-breakers, which allow to enlarge reliability of the systems of power supply by diminishing the number of multiple earth fault in electric network. Diminishing the number of multiple earth faults is attained by exception of switching overvoltage, because commutations of feeder circuit-breakers are carrying out when shunting circuit breaker is closed. The detection of damage in the feeder, when this method is used, is produced on the change of phase of current in the circuit of shunting circuit breaker after disconnecting of circuit-breaker of this feeder.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.