Abstract

Temporary overvoltage (TOV) is becoming one challenge for the integration of significant power electronics resources into a power system. To assess the risk of TOV in a Multi-Infeed Power Electronic System (MIPES), a worst-case estimation approach is proposed to assess TOV risk. The paper starts with analyzing the mechanism of TOV, which reveals that TOV is dominated by excessive reactive power resulting from comprehensive control laggings. Then, the principle of approximating the TOV for a Voltage Source Converter (VSC) connecting to an infinite bus is introduced within the context of the RMS model. After that, a method based on the concept of generalized short-circuit ratio for overvoltage (gSCR-TOV) is introduced to quantify the risk of TOV in a multi-bus system. This concept intends to permit screening to identify those nodes at greatest need for further EMT assessment. To localize these nodes, a concept of weighted sensitivity matrix is further proposed to pinpoint the bus subject to highest TOV in a MIPES. Finally, case studies of EMT time-domain simulations are carried out and verifies the effectiveness of the proposed methods.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.