Abstract
Grid codes stipulate that grid-connected voltage source converter (VSC) interfaced generation units should possess fault ride-through capability during grid faults. Resynchronization with the postfault grid is crucial for this purpose. However, it is not always easy for VSCs connected to a high-impedance weak grid to achieve resynchronization during severe grid faults. This article studies the loss of synchronism (LOS) of VSCs during grid faults. A nonlinear model describing the dynamics of the phase-locked loop (PLL) is developed, and a modified equal area criterion is utilized to identify the crucial factor affecting the resynchronization. The findings show that PLL’s integral regulator is unfavorable for the resynchronization since it probably causes the system operating point to enter negative damping zones and even reverse regulation zones, consequently resulting in LOS. A variable structure PLL method with great simplicity is proposed to improve the resynchronization capability. The method removes PLL’s integral regulator during grid faults to eliminate its unfavorable effect. Experimental and simulation comparisons with existing methods verify the performance of the method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Journal of Emerging and Selected Topics in Power Electronics
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.