Abstract

In this article, the transient synchronization process of the grid-connected voltage source converters (VSC) is studied detailly. Firstly, the phase-locked loop (PLL)-synchronized VSC is modeled according to the rotor motion equation of synchronous generator (SG). Furthermore, the VSC's damping ratio is derived, and the effects of the VSC's control parameters and the operation status on the equivalent power angle (EPA) is investigated. Moreover, the influence of the PLL's parameters and the voltage dips degree on the VSC's transient frequency behavior are analyzed. Analysis result reveals that the VSC's damping ratio decreases once the grid voltage drops, so that the EPA and frequency of the VSC may appear large overshoot and oscillation, which may trigger the frequency protection and deteriorate the VSC's transient stability. In order to ensure that the VSC can smoothly operate to new equilibrium points, an improved PLL is proposed, which can adaptively adjust the VSC's damping ratio for different voltage sags. The proposed method can not only reduce the overshoot of the EPA but also restrain the VSC's frequency dips degree. Finally, the simulations and experimental tests validate the effectiveness of the theoretical analysis.