Abstract
To accurately select the insulation level of submarine cables, an in-depth study should be conducted on the problem of temporary overvoltage attributed to long AC cables used in offshore wind power transmission. This study selected the offshore wind farm connected by single circuit submarine cables as the research object. In combination with the relevant current source characteristics and overvoltage protection strategy, this study theoretically analyzed the temporary overvoltage characteristics exhibited by submarine cables under no-load and load rejection conditions. In addition, the effects of submarine cable length, system short-circuit capacity, transmission capacity and overvoltage protection delay on the amplitude of temporary overvoltage were investigated. The voltage amplitude of load rejection temporary overvoltage showed a positive correlation with the transmitted power and the overvoltage protection delay of the fan converter. Shunt reactor could effectively suppress temporary overvoltage, and its installation position slightly affected the suppression effect.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.