Abstract

With the continuous development of power electronic devices and science and technology, cables and rectifiers, inverters, DC transmission equipment, and other nonlinear loads have been widely used in power systems. However, this causes harmonic pollution and large capacitive reactive power, which can affect the safe and stable operation of the power system. Based on the analysis of the reasons for the use of static var generator in the power grid and the existing conditions of even harmonic, the impedance analysis method was used to analyze the abnormal noise event of a transformer in a substation. Firstly, the equivalent impedance model diagram is drawn by the equivalent circuit method, and the equivalent impedance value of the system is calculated. A number of harmonic amplifications and the positions of the resonance point are calculated by MATLAB software. Secondly, the correctness of the above theoretical analysis is verified by field test and simulation model built in ETAP software. Finally, because of the abnormal noise of the transformer in a substation caused by harmonic amplification, three harmonic suppression measures are given.