Abstract

The vacuum interrupter-based DC circuit breaker is one of the most important equipments in the DC power system. The dielectric recovery (DR) of vacuum interrupter (VI) is essential for breaking reliability, especially on some occasions with ultra-large fault current such as the outlet of generator. To measure the DR of VI under high arcing current, an experiment circuit is designed and the DR under arcing current from 20 kA to 60 kA is presented in this paper. The influence of arcing current, contact separation, <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">di/dt</i> before current zero and arcing time on the DR is investigated. Particularly, it's found that under a specific arcing current, there exists an optimal arcing time for DR, and it shows a negative correlation with the arcing current.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.