Abstract

Abstract Previous research on radio interference in DC lines has focused on radio interference caused by corona discharge. But with the development of Modular Multilevel Converter Based High Voltage Direct Current (MMC-HVDC) systems, high frequency signals generated by fast switching of Insulate-Gate Bipolar Transistor (IGBT) are transmitted to Direct Current (DC) lines and radiate radio interference outward. On the one hand, the radio interference formula recommended by the dual-level DC transmission line recommended by International Special Committee on Radio Interference (CISPR) is calculated by the radio interference generated by the line corona discharge; On the other hand, by establishing a MMC-HVDC line model, analyse the high frequency signal transmission generated by the fast switching of IGBT in the Modular Multilevel Converter (MMC) to the radio interference generated by radiating outside the DC line. The results of the study show that the radio interference generated by high -frequency signals of IGBT fast switching will decrease with the length of the line. The radio interference value generated by corona discharge is 47.43 dB(μV/m), the radio interference generated by the high-frequency signal of IGBT fast switching is 40.83 dB(μV/m), which is too small than the radio interference of corona discharge.