AbstractA representative frequency dependent model (FDM) of an HVDC cable is important in ensuring HVDC systems are designed harmoniously. A model of the proposed and very long, 4200 km, AAPowerLink cables is implemented in PSCAD/EMTDC. The suitability of approximations required for efficient simulation are evaluated according to the anticipated cable specifications. In practice, a submarine cable of this length has between 40 to 80 field joints (FJ), which can be onerous to individually express and computationally expensive to model. Frequency domain analysis shows a minimum of 8 FJs is sufficient to represent the behaviour of the core voltage. The sensitivity of the FDM to cable parameters and operating conditions is assessed. The FDM is applied to establishing single ended fault location techniques. For a 4200 km cable these techniques can determine fault location to within 200 km (≈5%). Additional methods are explored to refine fault location estimates.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.