Abstract

Abstract No selective protection exists in the low-voltage level micro-grid integrated with DG presently. To deal with this problem, a new type of micro-grid protection scheme based on fault component is put forward. To implement this scheme, the micro-grid is divided into several regions, and each region is regarded as the target of protection. As a result, not only the scope of outage is decreased in accordance with the action of the protection, but the economic requirement of protection arrangement is met. Taking the negative sequence component as the basic characteristic quantity, a variety of asymmetric faults effectively can be identified successfully. Considering the adverse effects of unbalanced load and the switching of large capacity single phase load, a low-voltage supplement criterion is introduced. The effectiveness of this protection scheme is verified with EMTDC based simulation tests.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.