Abstract
The paper presents two new schemes of harmonic current reduction in distribution circuits. The first scheme aims at the reduction of harmonics generated by six pulse bridge rectifiers which are common nonlinear loads in industry. The new approach is based on injection of the third harmonic current into the transformer secondary. The current injected is generated in two passive filters connected between the outputs of the bridge and the common point of transformer secondary. The scheme is very effective, reducing harmonic distortion in the supply current from 27% to 4-5%. The second scheme presented aims at the reduction of harmonic distortion caused by fluorescent lamp systems. It assumes the installation of a series filter in the neutral conductor. A specially designed filter provides a low impedance path for the first harmonic current and high impedance for higher harmonics. Simulation and laboratory tests show significant reduction of harmonics in the neutral and phase conductors.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.