Abstract

This article evaluates the method of reducing power loss due to 3 <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">rd</sup> harmonic currents in a building that contains a significant level of electronic loads, by placing a passive filter in the neutral path. The initial power loss is obtained through current measurements in the phase and neutral conductors and knowledge of the resistance of these conductors and that of the transformer serving the facility. PSpice simulations are performed to determine the most suitable RL-C filter to minimize this loss. The losses are found to be not that significant due to existing reinforcements in the distribution circuit. The effect of filter placement on voltage distortion and capacitor resonance with the transformer leakage inductance are addressed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.