Abstract

The recognition of transient overvoltage characteristics is the premise of disturbance compensation of the transient overvoltage. Based on that, the recognition algorithm of transient overvoltage characteristics based on symmetrical components estimation was proposed. The generation mechanism of the transient overvoltage in gas insulated switchgear (GIS) was analyzed. Then, the transient overvoltage was measured via the capacitive sensor method. The three-phase voltage of ultra-high voltage grid was asymmetrical when the transient overvoltage appeared. At present, the asymmetrical three-phase voltage was decomposed into the superposition of a symmetrical positive-sequence component, a negative-sequence component, and a zero-sequence component via the symmetrical components estimation to build the superposition model. The model was decomposed via the trigonometric identity and the modified neural network of the least mean square learning rule was used to estimate the parameter vector of the characteristic quantity of the transient overvoltage in real time. The feasibility of the proposed algorithm was verified via comparing the simulation of the proposed algorithm and the algorithm based on dp transformation. The experimental results show that the proposed algorithm has the advantages of a small operand, high detection precision, and fast action.

Highlights

  • The gas insulated switchgear (GIS) has the advantages of a compact structure, less land occupation, and easy maintenance [1]

  • The transient overvoltage will generate the transient enclosure voltage (TEV) at the joint of the GIS shell and theouter lead, causing the problem of safety and secondary equipment insulation and the forming of the electromagnetic interference to the measurement and control equipment, which generates the malfunction of the secondary equipment [4,5]

  • The experimental investigation on transient attention from researchers, in which the overvoltage is called as very fast transient overvoltage with overvoltage in the extra-high voltage GIS is still scarce due to the restriction of test conditions and the most important characteristics of high amplitude and steep wave front

Read more

Summary

Introduction

The gas insulated switchgear (GIS) has the advantages of a compact structure, less land occupation, and easy maintenance [1]. It is widely applied in the 110 kV or above power grid. The transient overvoltage will generate the transient enclosure voltage (TEV) at the joint of the GIS shell and theouter lead, causing the problem of safety and secondary equipment insulation and the forming of the electromagnetic interference to the measurement and control equipment, which generates the malfunction of the secondary equipment [4,5].

Methods
Findings
Discussion
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.