Abstract

This paper presents the application of two digital filters working together for fast estimation of power systems symmetrical components. The three-phase unbalanced system is transformed to two phases using α–β-transformation. Using such a transformation, harmonics of order 3 and their multiples, in the input signal, are suppressed. Having identified the two-phase voltages, the positive and negative sequence phase voltage can be calculated using a constant transformation matrix. The zero sequence component is easily estimated by averaging the unbalanced three-phase voltage at every sample instant. Least error square algorithm is used to identify the magnitude and phase angle of sequence components from the available samples of the specified component.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.