Abstract

This paper discusses the Data-Based Mechanistic (DBM) approach to modelling the micro-climate in agricultural buildings. Here, the imperfect mixing processes that dominate the system behaviour during forced ventilation are first modelled objectively, in purely data-based terms, by continuous-time transfer function relationships. In their equivalent differential equation fonn, however, these models can be interpreted in terms of the Active Mixing Volume (AMV) concept, developed previously at Lancaster in connection with pollution transport in rivers and soils and, latterly, in modelling the microclimate of horticultural glasshouses. This can be compared with the incomplete mixing and control volume concepts that have been investigated previously at Leuven. The data used in the initial stages of the research project, as described in the paper, have been obtained from a series of planned ventilation experiments carried out in a large instrumented chamber at Leuven. The overall objectives of this collaborative study are two-fold: first, to gain a better understanding of the heat transfer and micro-climate dynamics in the chamber; and second, to develop models that can form the basis for the design of optimal ProportionalIntegral- Plus (PIP-LQ) climate control systems for livestock buildings of a kind used previously for controlling the micro-climate in horticultural glasshouses.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call