Abstract

Power quality disturbances cause equipment damage or financial losses. Therefore, the electric power system needs to identify and distinguish any power quality disturbances to reduce problems. This paper proposes hybrid methods combining FFT and ANFIS algorithm for detection of power quality disturbances. There are 11 types of power quality disturbances that can be detected, such as sag, swell, undervoltage, overvoltage, voltage flicker, voltage harmonic, sag + harmonic, swell + harmonic, undervoltage + harmonic, overvoltage + harmonic, and flicker + harmonic. The parameters used to detect disturbances are Vrms, Duration, THDv (Total Harmonic Distortion voltage), and Fluctuation-Count. The detection process starts by sensing voltage and calculating all the parameters, where THDv was obtained by Fast Fourier Transform. All the parameters such as Vrms, Duration, THDv, and Fluctuation-Count are processed by Adaptive Neuro-Fuzzy Inference System, and the result is the type of disturbance. Matlab simulations show that the suggested method performs outstandingly to identify 11 type of Power Quality Disturbances with 99.3% accuracy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.