Abstract

Fundamental phasor estimation is one of the most important jobs to be done by the digital protective relay (DPR). However, fault signals given to DPR consist of decaying DC (DDC) components, harmonics, and noise which can lead to inaccuracy in phasor estimation. Hence, for accurate results, digital filtering algorithms (DFAs) are mandatory to wipe out all these unwanted components. In modern DPR, discrete Fourier transform (DFT) is extensively used DFA for fundamental phasor estimation. However, the accuracy of DFT is affected by the presence of DDC. Hence, to tackle this problem, a new real-time fast DFA based on the mathematical morphology (MM) technique is put forward. First, the DDC components are filtered out using the morphological median filter (MMF) and are subtracted from the original fault signal. Afterwards, the fundamental phasor is extracted from the residual DDC-free signal using the DFT. Several computer-simulated, EMTP-generated, and real-field fault signals are used to examine the efficacy of the proposed DFA. In addition, the proposed DFA is compared with other existing techniques. The obtained results prove that the suggested DFA has vigorous performance in the presence of multiple DDC components, noise, and severe harmonic conditions with a low computational burden and high accuracy.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.