Abstract

An efficient noniterative method for ranking line outage contingencies in an AC-DC system based on overload and voltage deviation performance indices is developed. The method is based on the calculation of complex line outage current compensations using a coupled AC-DC load flow Jacobian matrix. The proposed method is further extended for the calculation of line outage distribution factors which could be very useful for reducing the computational burden in security constrained optimisation problems. A mathematical model for handling bus-type switching resulting from reactive power limit violations is also developed. Results for a modified IEEE 14-bus system have been obtained with the proposed method and are compared with those obtained by rigorous AC-DC load flow.< >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.