Abstract

A series of tests measuring HF signal attenuation were performed on a de-energized 15 kV three-phase power distribution feeder. The feeder consisted of a U-shaped line measuring approximately 208 m in length with varying line geometry around the circuit. RF signals in the range of 2 to 30 MHz were injected in one phase of the feeder and the propagated responses were measured at two locations along the feeder. Tests were conducted with and without shunt power equipment (distribution transformers, arresters and capacitors) connected to the feeder. The characteristic line impedance of different line geometries was calculated by analytical means and found to be consistent with experimental results. Attenuation and characteristic impedance were found to be relatively constant at frequencies between 15 and 30 MHz with minimal influence from line geometry and power equipment placement.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.