Abstract
This paper presents the study related to the power system stabilizer (PSS) design for northern regional power grid (NRPG) of India. The location of local PSS is suggested by participation factor approach. The power-voltage reference (PVr) characteristic of the suggested generator is used to obtain the compensator block of the local PSS. Internal states are lost while performing model order reduction therefore, the shaft dynamics are not available in the reduced order model for disabling. Therefore compensating block has to be design by utilizing full order system. But, the gain of the PSS can be tuned by utilizing the reduced order model. Next, the model order reduction (MOR) is performed with a target on preserving the characteristics and behavior of dominant inter-area mode in reduced order model (ROM). Thereafter, the tuned gain using ROM is combined with compensator and washout filter to obtain PSS for 44th generator (G44). The performance of designed PSS is investigated under five cases of disturbances.