Abstract

In this paper, a fault direction estimation algorithm is proposed for a double-circuit line with thyristor controlled series capacitor (TCSC) using principal component analysis (PCA)-based technique. In case of PCA, an orthogonal transformation is used to convert correlated variables into linearly uncorrelated variables called principal components. Fault in such a compensated line leads to voltage inversion, current inversion, and subsynchronous resonance situations, which affect the performance of the conventional direction estimation process. Transients associated with metal oxide varistor (MOV) operation and control action associated with TCSC, further modulate equivalent impedance of TCSC and MOV combination. In the proposed approach, PCA of angles between positive and negative sequence components of voltage current has been carried out to extract the pattern and to declare the fault direction accurately. The double-circuit line with TCSC is simulated using PSCAD/EMTDC software. The performance of the proposed technique is tested for numerous test cases, and it was found to be accurate.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call