Abstract

In this paper, a modified distance protection setting method is proposed to use the conventional distance relays for the transmission lines. The comprehensive studies regarding the impact of the thyristor-controlled series capacitor (TCSC) on a conventional distance relay are shown that the TCSC affects the operation of distance relays not only at the series compensated lines but also at the adjacent lines. The proposed method uses the equivalent impedance of the TCSC considering a metal oxide varistor (MOV), which is one of the overvoltage protection element for the TCSC to calculate the setting values which can prevent the mal-operation of the distance relays. To analyze and evaluate the performance of proposed method, a series of simulation studies were carried out with the PSS/E and PSCAD/EMTDC environment.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.