Abstract
ABSTRACTVoltage regulation of the single-phase UPS inverter has design challenges in terms of dynamic performances and control complexity. Widely used conventional integral controllers, such as proportional integral and proportional resonant in stationary frame (SF) of reference have limitations of either steady state error or implementation difficulties. Although a mature technique in three-phase applications, the synchronous reference frame (SRF) control scheme has not been exhaustively investigated for single-phase UPS inverters due to complex multiple transformations. This paper suggests a voltage control scheme which can be alternatively used in both stationary and synchronous reference frames. Three integral controllers namely, SF-proportional integral (SF-PI), SF-proportional resonant (SF-PR) and SRF-proportional integral (SRF-PI) are comparatively evaluated for steady state and transient performances. A systematic procedure for the design of control parameters with stability analysis in the frequency domain for the closed loop control system is also presented. Respective controllers are simulated in discrete time frame using MATLAB/Simulink and experimentally implemented using the TMS320F2812 Digital Signal Processor based laboratory prototype.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.