Abstract

With the increased use of partial discharge tests to assess the conduction of shielded distribution cable, PD signal frequency properties of such cables have become increasingly important. It is desirable to detect and locate the PD in the cable before breakdown occurs. Understanding the propagation phenomena of the PD signal in XLPE cable is important to detect and locate the PD signal. In this paper, transmission properties of PD signal were measured and analyzed on a 30m length and 15m length of 11 kV XLPE cable in the laboratory . The experimental results show a good agreement with the theoretical analysis. The paper describes the test results and discusses the PD signal attenuation in time and frequency domain and discusses this with reference to practical PD detection.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.