Study presents the results of the steam surface KCS-200-2 reconstruction. In order to maintain the dissolved oxygen concentration, according to the Code of Operation for Power Plants, the steam sparger was installed in condenser hotwell. Despite the abnormal air leakage level, reducing of dissolved oxygen concentration was reached. The dissolved oxygen concentration reduced, on average, by 2 times. As it was expected, in the cases of low inlet cooling water temperature, the final oxygen concentration did not reach the normal level. In last 3 tests the dissolved oxygen concentration was reduced to 19 mg /l. The results show a possibility of described reconstruction experience.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.