Abstract

This paper presents a new technique for the detection of islanding conditions in electrical power systems. This problem is especially prevalent in systems with significant penetrations of distributed renewable generation. The proposed technique is based on the application of principal component analysis (PCA) to data sets of wide-area frequency measurements, recorded by phasor measurement units. The PCA approach was able to detect islanding accurately and quickly when compared with conventional RoCoF techniques, as well as with the frequency difference and change-of-angle difference methods recently proposed in the literature. The reliability and accuracy of the proposed PCA approach is demonstrated by using a number of test cases, which consider islanding and nonislanding events. The test cases are based on real data, recorded from several phasor measurement units located in the U.K. power system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.