Abstract

This paper presents a very accurate method for water temperature prediction of outlet water from counter flow of cooling tower. This method was derived from the method of [hc A/Cpm] which is called NTU (Number of Transfer Units). The effect of the water and air mass flow rate, wet bulb temperature of the inlet air, outlet water temperature, tower range, and temperature approach have been studied. The results of comparison between the presented and the NTU methods show a very good match when the outlet water temperature is between 29 and 45°C and a difference reaches to 7.23% between 26 and 28°C. Another very good match has been noticed when the air mass flow rate is between 15.6 and 16.5 kg/s with difference reaches to 2.5 % when the air mass flow rate is between 10 and 15 kg/s. The last very good match has been noticed when the water mass flow rate is between 17.5 and 19 kg/s with the difference reaches to 1.2% when the water mass flow rate is (10 - 17 kg/s).